Notifier Italia | English

Youtube

Fire  >  ADDRESSABLE SYSTEMS  >  ADVANCED PANEL

AM-8000.4 4 LOOP FIRE DETECTION CONTROL PANEL WITH ADVANCED PROTOCOL

Addressable high speed microprocessor fire detection control panel, certified in accordance with EN 54-2 and EN 54-4. The control panel AM-8000.4 can drive 2 analog loops and it’s expandable to 4 using an additional LIB-8000 card installed inside the panel. Using the high speed CAN bus line it’s possible to expand the control panel AM-8000.4 from 4 to 32 loops through the connection with max 7 BB-8000 (expandable from 2 to 4 loops). Each loop, using the new Advanced protocol, can manageand supervise 159 sensors and 159 modules up to max 5088 sensors and 5088 modules. On the CAN-bus, that links AM-8000.4 with BB-8000, it’s possible to connect up to 8 LCD-8000-L displays in order to manage and supervise all the fire detection system. The display can be installed on the field or on the BB-8000. Each Box in the network is provided with power supply and backup battery certificate in accordance with EN 54-4.