AM2000N 2 LOOP ADDRESSABLE CONTROL PANEL

2 loop addressable fire detection panel for the management of addressable type systems. Each loop allows the connection of 99 detectors and 99 modules. The control panel allows to manage separate gas detection system, thanks to a special interface module, the display must be on a separate remote terminal for technical alarms only. Output sounder controlled, relay output for general alarm and fault. Two serial outputs in standard version with two optional through additional card. Standard outputs for 16 terminals and PCs for download/upload programming. Optional outputs for Ethernet (TCP / IP) connection and USB output for PC or printer, or output for connection to RS232/485 NOTE-FIRE-NET. Graphic display with 8 rows by 40 columns. Programmable text 32 characters each point and 32 characters each zone. 150 geographical zones and 400 groups with logical operators (AND, OR, DEL, etc...). 999 events archive. Auto programming of the loop with double address recognition. Signal for maintenance requirements for the detectors. In accordance with EN 54-2 and EN 54-4. Power supply 230VAC. Standard Power Supply 2,1A. 1A at 24VDC auxiliary power, with resettable and non resettable output. 12VDC charging of two batteries 17Ah. Dimensions: 483mm x 266mm x 111mm.