FL2022EI-HS FAAST SYSTEM 2 CHANNEL 2 DETECTORS

FAAST LT aspiration system 2 channels analyzes the smoke using 2 addressable high-sensitivity laser detectors. The aspiration is by means of the double fan and to the pipe provided with holes. This is in ABS with 100 meters of maximum length. The system incorporates a sensor for monitoring the continuity of the flow. Indication to a bright bar of led to pendulum of the air flow. Relays of alarm, of fault and sounder output. CPR certified in accordance with EN 54-20. External power supply for 18.5-31.5VDC. Maximum current up to 570mA (without sounder connected). The current stand-by from loop 900µA. Operating temperature: from -10°C to +55°C. Relative humidity up to 93% (non-condensing). Degree of protection IP 65. Dimensions: 403mm x 356mm x 135mm.